Home Fire Extinguishers
Fire Extinguishers PDF Print E-mail

Amerex manufactures an extensive variety of hand portable and wheeled fire extinguishers, both “compliance” (code required) and “specialty” types. “Specialty” type extinguishers are intended for use on particular types of hazards, so careful attention should be made to locating them in close proximity to the specific hazard they are meant to protect. It is natural for a person to use the extinguisher located nearest to a fire. The most current issue of NFPA-10 should be consulted for minimum recommended fire extinguisher types, placement and travel distances.

All Amerex extinguishers are manufactured and tested to ANSI/UL Standards.

  
 
DIFFERENCE CLASSES OF EXTINGUISHERS:
 
CLASS TYPES OF FIRES PICTURE SYMBOLS
    
 A  ORDINARY COMBUSTIBLES
 wood, paper, rubber, fabrics and many plastics
    
 B  FLAMMABLE LIQUIDS & BASES
 gasoline, oils, paint, lacquer and tar
    
C FIRE INVOLVING LIVE ELECTRICAL EQUIPMENT
  
    
   
 MODEL 240 EXTINGUISHER
   
  

Model 240 utilizes the cooling, soaking and penetrating effect of a 45-55 ft. stream of WATER. The 50 sec. discharge time makes it very effective for inexperienced operators for use on Class A fires. Protect from freezing by adding the Model 506 Loaded Stream/Anti-freeze charge. In areas with a high level chloride content water it may be corrosion protected by using the Model 507 charge.

SPECIFICATIONS
 WATER
Application
 Hose and Nozzle
U/L Rating   
 2A
Capacity   
 2½ Gal
Shipping Wt. (lbs.) (Empty)    
 
Height (in.) 
  24½
Width (in.)  
 9
Depth (Diam. - in.)   
 7
Range (Initial - ft.)   
 45 - 55
F. M. Approved 
  Yes
Discharge Time (sec.)
 50
Standard Bracket    Wall
Temperature Range
 +40°F to +120°F

Note: The Model  240 may be freeze protected to -40°F by adding a Model 506 Anti-Freeze charge

Polished Stainless Steel Cylinders

  •  All Metal Valve Construction
  • Leaves no powder residue
  • Maximum visibility during discharge
  • Novice friendly, easy to understand instructions
  • Bar Coded Labels

 



CLASS A

 
   
CARBON DIOXIDE EXTINGUISHER
   
  

Carbon Dioxide is discharged as a white cloud of “snow” which smothers a fire by eliminating oxygen. It is effective for Class B flammable liquids and is electrically non-conductive. Carbon Dioxide is a clean, non-contaminating, odorless gas.

SPECIFICATIONS
 
 Carbon Dioxide 
Size & Capacity (lbs)
  5 1015 20
Application
 Horn          Hose & Horn
Model Number
  322330
 331332
U/L Rating   
 5B:C
10B:C 10B:C10B:C
Shipping Wt. (lbs.)     14
28¼37¾
50¾
Height (in.)   17¾
2430
30
Width (in.) 1212
13
Depth (Diam. - in.)    
7
7
 8
Range (Initial - ft.)   
 3-8
Discharge Time (sec.)
 101012½ 19
F.M. Approved             Yes 
Standard Bracket             Wall 
Temperature Range
  -40°F to 120°F 
   

Rust free aluminum cylinders

  • All Metal Valve Construction
  • Meets many hospital medical equipment requirements
  • Independently test and approved for use in MRI facilities
  • Bar Coded Labels

 

 

CLASS B:C
 
   
 ABC DRY CHEMICAL EXTINGUISHER
   
  

ABC or Multi-Purpose extinguishers utilize a specially fluidized and siliconized mono ammonium phosphate dry chemical. It chemically insulates Class A fires by melting at approximately 350°F and coats surface to which it is applied. It smothers and breaks the chain reaction of Class B fires and will not conduct electricity back to the operator. Available in Wheeled and Stationary extinguishers.

SPECIFICATIONS
                         ABC Dry Chemical
Size & Capacity (lbs)
           5          10 Tall          20
Model Number
 B500/B500T
           B456
          A411
Application
   Hose & Nozzle 
U/L Rating   
 2A:10B:C
4A:80B:C
20A:120B:C
Shipping Wt. (lbs.)     9¼/ 9½ 1838
Height (in.)   15¼ 20
23¼
Width (in.) 10¼
Depth (Diam. - in.)    
5
 7
Range (Initial - ft.)   
 12-18
15-21
 15-21
Discharge Time (sec.)
 1420
30
F.M. Approved  Yes
Standard Bracket  Wall/Vehicle
 Wall Wall
Temperature Range
  -65°F to 120°F 

Dependable Drawn Steel Cylinders

  • All Metal Valve Construction
  • Easy and more economical to maintain and service
  • Bar Coded Labels

 

 
 

CLASS A:B:C
  
    
REGULAR DRY CHEMICAL EXTINGUISHERS
 
    
  

Regular extinguishers contain a siliconized sodium bicarbonate based dry chemical with free flowing and non-caking additives. Economical Class B & C protection with lower initial cost and recharging. This chemical smothers fires in flammable liquids and pressurized gases and will not conduct electricity back to the operator.

SPECIFICATIONS
                    Regular Dry Chemical
Size & Capacity (lbs)
           5          10 Tall          20
Model Number
 B409T
           B457
          A412
Application
  Nozzle Hose & Nozzle
U/L Rating   
 10B:C
60B:C
120B:C
Shipping Wt. (lbs.)      1838
Height (in.)   15¼ 20
23¼
Width (in.) 5½10¼
Depth (Diam. - in.)    
5
 7
Range (Initial - ft.)   
 12-18
15-21
 15-21
Discharge Time (sec.)
 102828
F.M. Approved  Yes
Standard Bracket  Wall/Vehicle
 Wall Wall
Temperature Range
  -65°F to 120°F 

Dependable Drawn Steel Cylinders

  • All Metal Valve Construction
  • Easy and more economical to maintain and service
  • Bar Coded Labels

 

 
 

CLASS B:C
  
    
For Wheeled Extinguishers options and further information please contact your local Sale representative or A.J. Stone Co. Ltd.  

 

 

 

 
FIRE POLICE EMS SAFETY
Copyright © AJ Stone LTD. 2008